|
| |
Running A Column Simulation
We are now ready to begin performing column calculations
since all the variables have been specified.
Figure 3

Running the Column Simulator
We are now ready to run the column simulator to obtain all the
dependent variables such as the overhead and bottom distillate
conditions, the condenser load and so on.
Double click on the
column to enter the environment in which the calculations will be
performed. When you enter the window you will find a screen that
looks like Figure 4. In order for HYSYS to perform calculations
the Degree of Freedom box in Figure 4 must be zero.
If it is –1, the problem is over specified, in our case it
is not because we have fully defined all the independent
variables. The independent variables must be activated for the
simulator to be run. In the specifications section are listed all
of the possible independent variables.
In order to select the
independent variable that we want to use for the run, we have to
check the active box. This is shown in Figure 4. Make sure that
all the independent variables we have selected are checked. In
our case, the reflux ratio should be the only one checked. Any
other box such as the Distillate Rate should be deactivated because we did not choose it as our independent variable.
Once
the boxes of the variables are not selected as independent
variables, the Degree of Freedom box becomes zero
and the column simulator is automatically solved. You will obtain
a "Converged" icon in the bottom indicating that the entire
column simulator is solved.

Results
To review your results you can either exit Figure 4 by
clicking on CLOSE and double clicking on the individual
streams to see the results or click on WORK SHEET shown in
Figure 4 to get the spreadsheet with the combined results. We
obtain a spreadsheet as shown by Figure 5. From this spreadsheet,
we can see that the overhead flowrate is 79.3273 lb/hr and the
bottom distillate flowrate is 83.6727lb/hr. By going out of the
screen and double clicking on the individual streams we notice
that the overhead concentrations for ethanol is 64.9% and for the
bottom distillate is 35.9% (mass fractions).

Additional Steady State Cases
Having worked through the set up process, we will now do some
cases to illustrate how HYSYS can be used to evaluate different
conditions as specified by the user.
Case 1:
Let us say that we would like to know what amount of steam
(the reboiler load in BTU/hr) would be needed to obtain an
overhead ethanol concentration of 55% using the same conditions
as we used in the setup. To solve that problem, follow these
steps:
- Click on SPECS as shown in Figure 5
- Once there, you will need to import the variable you will
want to specify which is the overhead ethanol concentration. To
do so, click on ADD, you will obtain a window like the one
shown in Figure 6. Select COMPONENT RATIO then click on
ADD SPEC(s). A Comp Ratio Spec window will
appear. In this window you will need to specify what you want the
concentration to be (0.55). In the Name box you can leave
it as is or put any name you want. In the Stage box, you
need to specify which column stage you want to have the
concentration to be 0.55. To do so, click on
"<<Stage>>" then on the arrow in the top right corner
of the screen. There among all the choices offered, pick
CONDENSER, that is the overhead concentration. In the next
box, Flow basis, select what basis you want. Since we are
specifying mass fraction, click on the arrow and choose MASS
FRACTION. The overhead is liquid so we will leave the
Phase box as is. In Spec Value, enter 0.55, the value we
would like the overhead ethanol concentration to be. Then in the
Components box select ethanol by clicking on
"<<Components >>" and then clicking at the top arrow.
Once all this is done, click on CLOSE and the
concentration will be added in the Column Specification section.
- The next step is to delete the reboiler duty we had input
earlier to find the concentration. To do so, click on CLOSE to
go back to the graphic environment then double click on the
reboiler duty stream (in our case called Qr). Once you get the
Energy Stream window, click on the Heat Flow box then press
DELETE in the keyboard, then exit the window.
Now go back in the monitor screen by double clicking on the
distillation column. When in the column window environment,
click on MONITOR at the bottom of the screen to go to the Monitor
window. Once there you will notice that the degree of freedom
value is 1. The problem is under specified because you have not
yet activated the concentration specification. Scroll down the
specification column and click on the Activate box for the Comp
Fraction. The degree of freedom will be zero and the column will
automatically calculate the variables. Once the
“Converged” signal appears at the bottom of the
window, you can go back at the reboiler duty stream to get the
new calculated value for the heat duty, which is in this case:
206,730 BTU/hr.
Figure 6

Case 2:
In the second case let us say that we would like to know the
reflux ratio that would give an ethanol concentration of 80% with
a reboiler duty of 300,000 BTU/hr using the same feed
specifications as in the setup discussion. To solve this problem,
do the following:
- First, in the Monitor window, deactivate the
Reflux Ratio box. Then go under the Specified Value
column click on the current value of the reflux ratio. Then press
DELETE on the keyboard to empty the box. Then go in the
reboiler duty stream and input 320,000 BTU/hr. Go back to the
monitor screen by double clicking on the distillation
column.
- The next step is to input the concentration of ethanol
desired. Go again under the Specified Value column and go
to the Comp Fraction box, click on it. Go in the bar at
the top of the screen and input 0.8. Then activate the box by
clicking the activation box under the Active column. HYSYS
will automatically solve the system. Once the "Converged" signal
appears at the bottom of the window, click on UPDATE
INACTIVE then scroll up to see the reflux ratio necessary to
have 80 % ethanol at 320,000 BTU/hr. The reflux ratio needed is:
17.78
Dynamic Models
The steady state model is useful for modeling operations after they have
leveled off and have attained to steady state conditions. Also of interest
is how the column reaches steady state and what happens when set points on the
column control system are changed. The modeling of a column attaining
steady state is discussed next.
|